Chao Gong and colleagues at the State Grid Jibei Electric Power Co., Ltd. Electric Power Science Research Institute in Beijing have investigated a hybrid capacitor topology for grid-forming static var generators (SVGs).
Published in Frontiers in Energy Research on November 24, 2026, their peer-reviewed study combines supercapacitors, an electrolytic-capacitor branch and partial-power conversion to reduce supercapacitor requirements—demonstrated through simulation rather than hardware testing.
Key takeaways
- In the modeled 10 kW, 800 V SVG, the supercapacitor bank falls from 297 to 75 identical 3.0 V/50 F cells: a 74.75% reduction relative to the specified directly connected reference.
- The proposed arrangement operates nominally with 200 V across the supercapacitor bank and 600 V across a 12.5 mF electrolytic-capacitor branch.
- The auxiliary bidirectional converter is rated at 2.114 kW, including a 20% margin over simulated peak processed power—21.14% of the SVG rating.
- During consecutive frequency disturbances at 1 Hz/s, individual decline-stage peak support is approximately 1.52% lower, but support at the reference system’s peak instant is 16.44% lower. Similar peak magnitudes do not mean identical response.
Background
A conventional SVG mainly exchanges reactive power with the grid. Adding grid-forming control and an energy reservoir allows it to exchange transient active power as well, supporting frequency during disturbances. That active-power contribution must come from stored energy; control software cannot supply it independently of the DC-side hardware.
For approximately constant capacitance, usable energy is
The allowable voltage excursion therefore matters alongside capacitance. A supercapacitor bank connected directly across a high-voltage DC link requires many low-voltage cells in series, even when the transient energy requirement is modest.
The paper distinguishes this direct-connected arrangement from earlier full-power DC/DC-interfaced storage architectures. The latter decouple storage voltage from bus voltage, but process the transferred storage power through an additional converter.
The proposed alternative shares the DC voltage between two capacitor branches. For the broader distinction between energy buffering, ripple-current duty and local decoupling, see DC-Link Capacitors.
What the researchers found
How the hybrid capacitor topology works
The supercapacitor bank and electrolytic-capacitor branch are connected in series, so their voltages sum to the physical DC-link voltage. A bidirectional partial-power converter regulates the electrolytic branch and manages voltage allocation.
During the initial disturbance, the directly connected supercapacitor provides a fast energy path. The auxiliary converter remains active: it is not simply switched off during support and enabled afterward. During recovery, it redistributes branch energy and restores voltage allocation, while net replenishment of total stored energy requires exchange with the AC grid.
The comparison uses MATLAB/Simulink average-value converter models with a fixed-step solver and a 50 µs time step. Both configurations have a nominal local equivalent inertia of approximately 1.005 s under the implemented synchronization mapping.
| Parameter | Direct-connected reference | Proposed series arrangement |
|---|---|---|
| Nominal DC-link voltage | 800 V | 800 V |
| Nominal supercapacitor voltage | 800 V | 200 V |
| Supercapacitor configuration | 297 series cells, one string | 75 series cells, one string |
| Typical bank capacitance | 0.16835 F | 0.66667 F |
| Minimum bank capacitance | 0.15152 F | 0.60000 F |
| Typical / maximum beginning-of-life bank ESR | 2.970 / 4.752 Ω | 0.750 / 1.200 Ω |
| Auxiliary electrolytic branch | None | 12.5 mF at 600 V nominal |
| Auxiliary converter rating | None | 2.114 kW |
Table conditions: the paper’s 10 kW, 50 Hz model; identical 3.0 V/50 F cells, with 45 F minimum cell capacitance. Cell-count selection uses a 2.7 V nominal design ceiling. ESR values are the paper’s beginning-of-life bank parameters, not measurements of assembled prototypes.
The control comparison also requires more than substituting capacitor values. The reference synchronizes using its physical DC-link voltage; the proposed system uses an energy-equivalent voltage calculated from both capacitor-branch voltages. This gives a common nominal energy-to-frequency mapping without assuming identical internal dynamics.
Consecutive disturbances descend from 50 Hz to 49.6, 49.5 and 49.4 Hz, then return at the same 1 Hz/s rate. Their total durations are 0.8, 1.0 and 1.2 s.
Individual decline-stage peaks are approximately 447.31 W for the reference and 440.49 W for the proposed system. However, their peak times differ by 101.6 ms. At the reference peak instant, the proposed output is approximately 373.76 W.
Across the complete events, the maximum normalized instantaneous power difference reaches 30.23% during frequency return. Normalized RMS differences are 9.08–10.79%. These results support comparable peak magnitude under the tested conditions, not waveform equivalence.
Why it matters for passive components
The principal result is architectural, not a new dielectric or electrode material. Lowering the supercapacitor bank’s nominal voltage removes much of the series-cell requirement imposed by the bus.
Fewer series cells also reduce bank ESR for the same cell type. Nevertheless, system losses cannot be inferred from ESR alone: branch currents change, and the auxiliary converter introduces additional losses and hardware.
The reported cell-count reduction applies equally to summed cell mass and geometrical cell volume because the comparison uses identical cells. It does not establish the same reduction in complete equipment mass, enclosure volume or cost. The electrolytic bank, converter, inductor, cooling, insulation and protection must all be included.
Another useful finding is the difference between energy sizing and commercially realizable banks. The theoretical capacitance lower bounds are 3.766 mF for the reference and 54.537 mF for the proposed arrangement, using the paper’s voltage boundaries and energy margins. Both selected banks substantially exceed those bounds because series-cell realization imposes its own constraints.
Reducing cell count may simplify monitoring and interconnection, but does not eliminate cell-voltage imbalance. The practical requirements remain those discussed in Supercapacitor Balancing Methods.
From lab to component
This is a simulation-stage system concept, not a tested component assembly. An editorial maturity estimate is TRL 2–3: the operating principle and analytical design are supported numerically, but laboratory hardware validation remains necessary.
The demonstrated voltage range is particularly important. In consecutive-event simulations, the supercapacitor remains between approximately 198.130 and 200.101 V, while the electrolytic branch remains between 599.303 and 601.395 V.
By contrast, the theoretical supercapacitor sizing range extends from approximately 22.25 to 225 V. The authors explicitly distinguish that energy-sizing envelope from the converter’s dynamically validated range. The selected converter rating must not be assumed valid throughout the broader envelope.
Average-value simulation also leaves switching ripple, parasitic inductance, electromagnetic compatibility and detailed component heating unresolved. Positive local DC/DC control-loop stability margins do not prove stability of the complete grid-forming converter and grid.
Production assessment would additionally require an orderable electrolytic-bank implementation, thermal and lifetime verification, cell balancing, startup and fault handling, and a complete bill-of-materials comparison. No manufacturing-process or materials-compliance advantage follows from the topology alone.
What engineers should watch
- Hardware correlation: measured branch currents, support waveforms and energy balance against the average-value model.
- Wider voltage operation: converter current limits and control behavior away from the demonstrated near-nominal range.
- Response requirements: support at specified instants and recovery behavior, rather than only independently occurring peaks.
- Electrolytic-bank qualification: ripple-current spectrum, voltage sharing, hotspot temperature and service life.
- Aging and imbalance: reduced capacitance, increased ESR, leakage spread and balancing losses across the mission profile.
- Complete-system economics: installed mass, volume, efficiency and cost compared with both direct-connected and DC/DC-interfaced alternatives.
Summary
The study demonstrates numerically that series voltage sharing can substantially reduce supercapacitor cell count in a specified grid-forming SVG while retaining similar individual peak-support magnitude. The saving comes with an electrolytic branch, an auxiliary converter and altered transient behavior.
For designers, the central lesson is to size the capacitor bank, energy-state control and converter together. Cell-count savings are meaningful only when the complete assembly meets the required support timing, operating envelope and reliability targets.
Source
This article is based on the peer-reviewed paper published in Frontiers in Energy Research, available through gold open access under a Creative Commons Attribution license, CC BY. No matching institutional press release was located in the searches performed. These are simulation-based research results, not qualified commercial components; design decisions should await manufacturer data and appropriate component and system qualification.
References
- Chao Gong, Yaohan Wang, Pengliang Xu, Haitao Liu and Yan Li, “Grid-forming SVG DC-side hybrid capacitor series topology and capacity design method,” Frontiers in Energy Research, vol. 14, article 1890252, November 24, 2026. https://doi.org/10.3389/fenrg.2026.1890252. Gold open access; CC BY. DOI-resolved publisher text supplied the topology, methods and numerical comparisons; a second publisher rendering confirmed acceptance and licensing information.